Journeyman Electrician Exam-Day Cheat Sheet

High-yield reference matrices, critical rules, classification charts, and formula cheat sheets for the Journeyman Electrician Exam (NEC / NFPA 70).

📌 Quick Summary / Core Test Principles:NEC Quick Reference: Continuous Load = Noncontinuous + 125% continuous load (NEC 210.19). Conductor Ampacity: 75°C terminal rating governs equipment terminations <= 100A / 14-1 AWG unless listed otherwise (NEC 110.14(C)). Grounding: Table 250.66 sizes Grounding Electrode Conductor based on largest ungrounded service conductor. Table 250.122 sizes Equipment Grounding Conductor based on upstream OCPD rating. Motors: Branch circuit conductor sized at 125% of motor Full Load Current (FLC from Tables 430.248/250, NOT nameplate). Inverse time circuit breaker OCPD max rating = 250% FLC (NEC Table 430.52). Conduit Fill: 1 conductor = 53%, 2 conductors = 31%, 3+ conductors = 40% (Chapter 9, Table 1).
Conductor Sizing

NEC Table 310.16 Allowable Ampacities of Insulated Conductors (Copper)

Conductor Size (AWG/kcmil)60°C (TW, UF)75°C (THWN, XHHW)90°C (THHN, XHHW-2)Standard Overcurrent Protection
14 AWG15 A20 A25 A15 A (NEC 240.4(D))
12 AWG20 A25 A30 A20 A (NEC 240.4(D))
10 AWG30 A35 A40 A30 A (NEC 240.4(D))
8 AWG40 A50 A55 A40 A (60°C) / 50 A (75°C)
6 AWG55 A65 A75 A60 A (75°C)
4 AWG70 A85 A95 A70 A (60°C) / 85 A (75°C)
2 AWG95 A115 A130 A100 A (60°C) / 115 A (75°C)
1/0 AWG125 A150 A170 A125 A (60°C) / 150 A (75°C)
2/0 AWG145 A175 A195 A175 A (75°C)
4/0 AWG195 A230 A260 A200 A (60°C) / 225 A (75°C)
💡 Pro Tip:Terminations on equipment rated 100A or less default to 60°C ampacity unless explicitly marked for 75°C (NEC 110.14(C)(1)(a)).
Grounding Standards

NEC Table 250.66 Grounding Electrode Conductor (GEC) Sizing Matrix

Largest Service Conductor (Copper)Largest Service Conductor (Aluminum)GEC Size (Copper)GEC Size (Aluminum)
2 AWG or smaller1/0 AWG or smaller8 AWG6 AWG
1 AWG or 1/0 AWG2/0 or 3/0 AWG6 AWG4 AWG
2/0 or 3/0 AWG4/0 AWG or 250 kcmil4 AWG2 AWG
Over 3/0 thru 350 kcmilOver 250 thru 500 kcmil2 AWG1/0 AWG
Over 350 thru 600 kcmilOver 500 thru 900 kcmil1/0 AWG3/0 AWG
Over 600 thru 1100 kcmilOver 900 thru 1750 kcmil2/0 AWG4/0 AWG
Over 1100 kcmilOver 1750 kcmil3/0 AWG250 kcmil
💡 Pro Tip:Special caps apply: Ground rod sole connection max 6 AWG Cu (250.66(A)); Concrete-encased Ufer ground sole connection max 4 AWG Cu (250.66(B)); Ground ring max 2 AWG Cu (250.66(C)).
Equipment Grounding

NEC Table 250.122 Equipment Grounding Conductor (EGC) Sizing

Overcurrent Device Rating (Amperes)Copper Conductor Size (AWG)Aluminum Conductor Size (AWG)Proportional Upsizing Rule
15 A14 AWG12 AWGMandatory proportional increase if ungrounded conductors upsized
20 A12 AWG10 AWGEGC must be increased in circular mils ratio per NEC 250.122(B)
30 A10 AWG8 AWGApplicable when conductors are upsized for voltage drop
40 A / 60 A10 AWG8 AWGTable 250.122 establishes minimum cross-sectional area
100 A8 AWG6 AWGBonding bushings required for service raceways
200 A6 AWG4 AWGRaceway cannot serve as EGC if ground continuity broken
400 A3 AWG1 AWGMultiple parallel raceways require full-size EGC in each conduit
💡 Pro Tip:When conductors are increased in size for voltage drop, the EGC must be increased proportionately in circular mil area (NEC 250.122(B)).
Conduit & Raceways

NEC Chapter 9 Table 1 Conduit Fill Allowable Percentages

Number of Conductors in RacewayMaximum Cross-Sectional Fill (%)Applicable Conduit TypesCommon Code Application
1 Conductor53%EMT, RMC, IMC, PVC (Sch 40/80)Single ground wire or heavy lead feeder
2 Conductors31%EMT, RMC, IMC, PVC (Sch 40/80)Two-wire branch circuits or single-phase runs without ground
Over 2 Conductors (3+)40%EMT, RMC, IMC, PVC (Sch 40/80)Standard 3-wire and 4-wire multiwire branch circuits and feeders
Nipple <= 24 Inches (600 mm)60%All approved raceway nipplesNo derating required per Note 4 to Chapter 9 tables
Cable with Elliptical Cross-SectionBased on major diameterAll approved racewaysTreated as single round cable using largest diameter dimension
💡 Pro Tip:Conduit nipples 24 inches or less can be filled to 60% and do NOT require ampacity adjustment derating (Chapter 9, Note 4).
Box Fill Calculations

NEC Table 314.16(B) Volume Allowance Required per Conductor

Conductor Size (AWG)Free Space Required per Conductor (cu in)Device Allowance FactorGround Conductor Factor
18 AWG1.50 cu. in.Double volume allowance (2x)Single volume for up to 4 grounds; 1/4 volume per ground thereafter
16 AWG1.75 cu. in.Double volume allowance (2x)Single volume for up to 4 grounds; 1/4 volume per ground thereafter
14 AWG2.00 cu. in.4.00 cu. in. per switch/receptacle yoke2.00 cu. in. for all EGCs combined (up to 4)
12 AWG2.25 cu. in.4.50 cu. in. per switch/receptacle yoke2.25 cu. in. for all EGCs combined (up to 4)
10 AWG2.50 cu. in.5.00 cu. in. per switch/receptacle yoke2.50 cu. in. for all EGCs combined (up to 4)
8 AWG3.00 cu. in.6.00 cu. in. per switch/receptacle yoke3.00 cu. in. for all EGCs combined (up to 4)
6 AWG5.00 cu. in.10.00 cu. in. per switch/receptacle yoke5.00 cu. in. for all EGCs combined (up to 4)
💡 Pro Tip:One or more internal cable clamps count as ONE conductor volume based on the largest conductor in the box (NEC 314.16(B)(2)).
Motor Branch Circuits

NEC Table 430.52 Maximum Rating of Motor Branch-Circuit Protection

Motor TypeNontime-Delay FuseDual-Element Time-Delay FuseInverse-Time Circuit Breaker
Single-Phase Motors300%175%250%
AC Polyphase Squirrel-Cage (Normal)300%175%250%
Design B Energy-Efficient Motors300%175%250%
Wound Rotor AC Motors150%150%150%
Direct-Current (DC) Motors150%150%150%
💡 Pro Tip:If the calculated breaker percentage does not correspond to a standard rating in 240.6, the NEXT HIGHER standard rating is permitted (NEC 430.52(C)(1) Ex. 1).